Construction Products Regulation

European Construction Product Regulation for coaxial cables


The European Construction Product Regulation 305/2011 (CPR for short) sets uniform rules for the use of building products within buildings for all EU member states. The implementation of the CPR is regulated by DIN EN 50575: 2017-02. The objective of the CPR / DIN EN 50575 is to increase the fire safety in buildings.
 

 

As of July 1st, 2017, the coaxial cables of SSB-Electronic GmbH have a corresponding fire classification and service agreement, as the CPR provides. Correspondingly, the coaxial cables are CE marked.

The CE marking is clearly visible, readable and permanent on the product label.
Additional labeling, such as origin, description and fire behavior, can also be found in the labeling. As a manufacture, we provide each tested cable with a service declaration, which contains precise information about the fire behavior, which you can download at any time from our website.

 
Coaxial Cable Euroclass according to
EN 50575
Building Fire Safety
Requirements
Application Area Classification Criteria AVCP System
(Assessment and Verification of
Constancy of Performance)
Aircell 5 Eca low Cables for standard applications:
in buildings with low height or low volume of occupants, in appartments

Flame propagation
EN 60332-1-2
H ≤ 425 mm

System 3:
Initial type-testing by third-party notified testing laboratory

Factory production control (FCB) by manufacturer

Aircell 7
Ecoflex 10
Ecoflex 10 PLUS
Ecoflex 15
Ecoflex 15 PLUS
Aircom Premium
Ecoflex Multicore
Ecoflex 10 PLUS
Heatex

Ecoflex 10 FRNC



 
Cca
s1 d0 a1
high Cables for areas with
increased fire risk:

in tower buildings,
facilities, administration & office buildings, commercial buildings,
restaurants, hotels,
underground parking,
schools, prisons, leisure facilities, etc.

Flame propagation
EN 60332-1-2
H ≤ 425 mm

Heat release,
vertical
Flame spread
EN 50399
FS ≤ 2,0 m
THR ≤ 30 MJ
max. HRR ≤ 60 kW
FIGRA ≤ 300 W/s
flame source = 20,5 kW

Smoke production
EN 50399/EN 61034-2
s1, s1a, s1b, s2, s3

Acidity/Corrosivity
EN 60754-2
a1, a2, a3

Flaming droplets
EN 50399
d0, d1, d2
System 1+:
Initial type-testing by third-party notified product certification body

Continuous factory inspection by third-party notified product certification body

Continuous audit testing of samples by third-party notified product certification body

 

Factory production control (FCB) by manufacturer

 



 

Ecoflex 15 PLUS
Heatex

Ecoflex 15 FRNC





 
Cca
s2 d2 a1
Aircell 5 Heatex

Aircell 7 Heatex
Cca
s1 d0 a1
LCF14-50JFN
(RFS)
B2ca
s1a d1 a1
very high Cables for areas with
high fire risk:

in hospitals, care facilities,
day-care centers for children,
server rooms, road and
railway tunnels, facilities for storing substances with an increased risk of fire, etc.


 
SCF38-50JFN
SCF12-50JFN
LCF12-50JFN
LCF78-50JFNA
(RFS)
B2ca
s1a d0 a1

Download Declaration of Performance (DoP):


Download Declaration of Performance (DoP) of RFS CELLFLEX® cables:



All CELLFLEX® SCF/LCF cables with jacket option "J" have the Euroclass "F / not classified" because none of the CPR classes are fulfilled.


The products of SSB-Electronic GmbH are therefore safe, tested, classified and thus fully comply with European legislation.